Overview
Batteries lose capacity with age, so most projects add capacity a few years in. PVX.AI sizes that addition and can reserve pads for it from the start. Noise contours show how far the sound of the yard carries.
In the BESS Designer these tools sit in four places: the augmentation inputs in Settings, the reserve pad options in Placement, the noise contours in Checks and the augmentation report in Reports.
Prerequisites
Units placed. For the best estimate, use an enclosure with degradation and noise values from the datasheet.
Step-by-Step Guide
1. Set the planning inputs
In the Settings step, click Configuration… and enter Horizon (years) and Cycles per year under Augmentation. The plan is sized at the end of the horizon.
2. Decide whether to reserve pads
On the Placement step in fit to capacity mode, tick Plan augmentation reserve pads before auto-placement to place spare pads next to the energized units. Reserve pads are drawn hatched and are excluded from energy totals, cabling, yield and noise. They are included in compliance checks and grading.
3. Open the augmentation report
In the Reports step, click Augmentation. The BESS Augmentation report shows the augmentation year, the required MWh, the reserve pads recommended against those present, and the energy a reserve pad still has at the end of the horizon. A table lists each transformer with Rated, Current loading, Reserve pads and Projected loading. Loading above 100 percent is highlighted. The report lists its assumptions, including any default used for missing catalog data.
The report recommends pads even when none were reserved at placement, so a recommendation does not mean pads exist in the drawing.
4. Adjust the reserve fleet
On the Placement step, click Reserve pads and pick a unit to switch it between energized and reserve. Then click Re-run in the report.
5. Draw the noise contours
In the Checks step, click Noise. PVX.AI draws labelled 45, 55 and 65 dBA rings on the PVXAI_BESS_Noise layer from the noise data of each enclosure and PCS skid. Sources without noise data are listed in the message, not estimated. Running it again redraws the rings.
Tips & Recommendations
- The noise model is a planning estimate: sound spreads from each source with no ground absorption, barriers or directivity.
- Levels above 55 dBA at tagged lot lines appear as warnings in the compliance report. Reserve pads contribute no noise.
- In a custom enclosure, fill in Noise (dBA) and Ref. Dist. (m), plus PCS Noise (dBA) and PCS Ref. Dist. (m) for DC blocks, so the contours include every source.
- Every figure in the augmentation report is an estimate for planning, not a warranty calculation.