Overview
The Settings step of the BESS Designer sets the design basis: which storage unit you place, how much of its energy is usable, the placement defaults and the augmentation inputs. Its header shows the selected enclosure and its usable energy in kWh with the calculation behind it.
This guide also covers the enclosure catalog, where you add a container that is not in the list yet.
Prerequisites
Open the BESS Designer from Electrical sub-tab > Electrical Design > BESS Designer. The BESS Area and Verifications steps can be done before or after this one.
Step-by-Step Guide
1. Check the enclosure catalog
Open Database > Products > BESS Enclosures. The list shows manufacturer, model, block type, energy (kWh), power (kW), size and origin. Type a manufacturer or model in the search box to filter.
If your container is missing, click New Enclosure. The form has the sections Identity, Dimensions, Energy / Power, Degradation / SoC, Maintenance Clearances, Fire / Noise and Power Conversion (PCS). Set Block Type to AC (integrated PCS) or DC (needs PCS skid). Only custom enclosures can be edited or deleted.
2. Open the configuration window
In the Settings step, click Configuration…. The BESS Configuration window holds the storage unit, the depth of discharge, the placement defaults and the augmentation inputs.
3. Choose the storage unit
Under Storage unit, click Browse… and pick an enclosure from the list. This is the unit that auto-placement uses. If it is a DC block, plan for a PCS skid next to each container.
4. Set the depth of discharge
Under Storage energy, the window shows the nameplate energy of the unit. Move the Depth of discharge slider (70% to 100%). Usable energy updates as nameplate multiplied by DoD. Placement, compliance and reports all use this usable value, so use the DoD from the manufacturer’s warranty or your energy model.
5. Set the placement defaults
- Default spacing: the smallest gap between units along a row. Auto-placement never packs tighter than this, even when the code and maintenance clearances would allow it.
- Naming prefix: the prefix for unit names, for example BESS.
- Row azimuth (°): leave blank to align the rows with the longest edge of the BESS area, or enter a value to force a row direction.
- Default coupling: AC-coupled (unit connects to a transformer) or DC-coupled (unit connects to an inverter).
6. Set the augmentation inputs and save
Under Augmentation, enter Horizon (years) and Cycles per year. The augmentation report and the optional reserve pads use them to project how much usable energy the fleet loses over time. Click Save.
Tips & Recommendations
- The capacity target is set on the Placement step, the fire code on the Verifications step and the pad grading parameters on the Grading step. The configuration window no longer holds them.
- Tick Has UL 9540A test data in a custom enclosure only when the manufacturer has a UL 9540A test report. It allows the reduced exposure setback in the compliance rules.
- Degradation and noise values are optional. When one is missing, the augmentation planner uses a conservative default and says so, and the noise model lists the unit as having no data. Enter datasheet values for the best results.
- Settings are stored in the drawing and travel with it.